LAND, an AMETEK Company, designs and manufactures a range of gas analyzers for monitoring combustion efficiency, pollutant emissions, opacity, dust and particulate matter concentration, coal fire detection and gas turbine blade temperatures.
|
|
Mill and Silo Fire Detector Download printable brochure
This detector provides advance warning of the onset of coal mill and silo fires through the early detection of the build-up of carbon monoxide in the mill.
Key Features
- Advance fire detection system
-
Specially designed for fire detection on coal mills and silos
- Continuous self-checking of measurement integrity
- Tailored to each application/plant
-
Standard analog and discrete contact outputs
Key Benefits
-
Protect expensive mill equipment and prevent downtime
- Robust, low maintenance system
- High level of reading confidence
- Easy connection to plant control equipment
This detector provides advance warning of the onset of coal mill and silo fires through the early detection of the build-up of carbon monoxide in the mill.
Key Features
-
Advance fire detection system
-
Specially designed for fire detection on coal mills and silos
- Continuous self-checking of measurement integrity
- Tailored to each application/plant
-
Standard analog and discrete contact outputs
Key Benefits
-
Protect expensive mill equipment and prevent downtime
- Robust, low maintenance system
- High level of reading confidence
- Easy connection to plant control equipment
|
|
|
Mill and Silo Fire Detector Specifications
|
CO Ranges (selectable)
|
0-100 up to 4000 ppm in 50 ppm steps or
0-100 up to 5000 mg/nm3 in steps of 50 mg/nm3
|
|
Resolution
|
1 ppm/ 1 mg/nm3
|
|
Linearity
|
<2% of range
|
|
Zero Drift
|
<2% of range per month
|
|
Span Drift
|
<2% of range per month
|
|
Optional O2 Ranges (selectable)
|
0-5% to 0-25%
|
|
Calibration Method
|
Automatic
2-point calibration span and zero
Microprocessor controlled
|
|
Analog Output
|
Single, isolated current loop for each CO level and O2 if fitted
0, 2 or 4 mA to 10 to 20 mA
|
|
Relay Output
|
2 x Level Alarms; System OK; Calibration/Maintenance
|
|
Relay Rating
|
Isolated changeover S.P. 1 A @ 240 VAC or
5 A @ 240 VDC resistive
|
|
Operating Temperature
|
0 to 45ºC (32 to 113ºF) standard
-20ºC (-4ºF) with optional case heater
50ºC (122ºF) with optional air conditioner
|
|
Power Supply
|
83 VAC to 132 VAC or 165 to 264 V, 50-60 Hz
|
|
Dimensions (HxWxD)
|
600 mm x 600 mm x350 mm (24 in x 24 in x 14 in)
|
|
Weight
|
53 kg (117 lb)
|
|
|
|
Ametek Main Page - Land - Thermox - Western Research - Process Instruments - Dycor - Chandler
|
|
|